Different transformer models are examined for the calculation of the no-load losses using finite element analysis. Two-dimensional and three-dimensional finite element analyses are used for the simulation of the transformer. Results of the finite element method are also compared with the experimental results. The Result shows that 3-dimensional provide high accuracy as compared to the 2 dimensional full and half model. However, the 2-dimensional half model is the less time-consuming method as compared to the 3 and 2-dimensional full model. Simulation time duration taken by the different models of the transformer is also compared. The difference between the 3-dimensional finite element method and experimental results are less than 3%. These numerical methods can help transformer designers to minimize the development of the prototype transformers.
No-load losses Iron losses Finite element analysis Power transformer Core losses Design optimization
Subjects | Engineering |
---|---|
Journal Section | Articles |
Authors | |
Publication Date | August 23, 2017 |
Acceptance Date | August 16, 2017 |
Published in Issue | Year 2017 Volume: 9 Issue: 3 |