Environmental risk analysis of electromagnetic field levels in power lines for smart grid infrastructure

Abstract

Smart grids bring more electrical equipment into cities, so the fields around this equipment need to be checked. Electric field strength (E) and magnetic flux density (B) in an underground transformer room, under a 380 kV, 50 Hz transmission line and near low and medium voltage distribution lines measured and expressed each reading as an exposure ratio (ER), i.e. as a percentage of the corresponding ICNIRP public reference level. The largest values were found 1 m above ground below the center conductor of the 380 kV line, where E was 1.396 kV/m (ER 27.9%) and B was 4.191 µT (ER 4.2%). For the same line, a three phase Biot–Savart expression came within about 4% of the measured B, while an ANSYS Maxwell model gave values 7%–21% above the analytical estimate over the current cases studied. On the risk scale adopted here, most locations fell into Category I or II. The transmission corridor was placed in Category III because of its electric field, even though no reading exceeded an ICNIRP reference level. The comparison also shows that the dominant field component differs between sources: E under the 380 kV line, B next to the transformer.

Keywords

Supporting Institution

Sivas Cumhuriyet University Renewable Energy Research Center (CUYEM), Sustainability Coordinating Office

Thanks

This study is derived from master's thesis which completed by Hami KURT at the Department of Energy Science and Technology Engineering, Graduate Institute of Science, Sivas Cumhuriyet University. We would like to thank the Renewable Energy Research Center (CUYEM) for their support of this study and TEİAŞ for their support in field measurements, and all institution employees for their contributions.

References

  1. [1] H. Kurt, "Risk analysis of electromagnetic field levels of transmission and distribution lines for smart grid infrastructure," M.S. thesis, Dept. Energy Sci. Technol. Eng., Sivas Cumhuriyet Univ., Sivas, Türkiye, 2023, pp. 75–79.
  2. [2] J. Park, E. Jeong, and G. Seomun, "Extremely low-frequency magnetic fields exposure measurement during lessons in elementary schools," Int. J. Environ. Res. Public Health, vol. 17, no. 15, Art. no. 5284, 2020, doi: 10.3390/ijerph17155284.
  3. [3] D. Baaken, D. Wollschläger, T. Samaras, J. Schüz, and I. Deltour, "Exposure to extremely low-frequency magnetic fields in low- and middle-income countries: An overview," Radiat. Prot. Dosim., vol. 191, no. 4, pp. 487–500, 2020, doi: 10.1093/rpd/ncaa172.
  4. [4] M. Landini, G. Mazzanti, and R. Mandrioli, "Procedure for verifying population exposure limits to the magnetic field from double-circuit overhead power lines," Electricity, vol. 2, no. 3, pp. 342–358, 2021, doi: 10.3390/electricity2030021.
  5. [5] L. S. Litzbarski et al., "The assessment of the influence of low-frequency electromagnetic fields originating from power infrastructure on human health," Appl. Sci., vol. 14, no. 21, Art. no. 9668, 2024, doi: 10.3390/app14219668.
  6. [6] H. Tian et al., "System-level biological effects of extremely low-frequency electromagnetic fields: An in vivo experimental review," Front. Neurosci., vol. 17, Art. no. 1247021, 2023, doi: 10.3389/fnins.2023.1247021.
  7. [7] Bilgi Teknolojileri ve İletişim Kurumu, "Ölçüm Takip Sistemi." [Online]. Available: https://www.btk.gov.tr/olcum-takip-sistemi (accessed Dec. 12, 2024).
  8. [8] K. Deprez, T. Van de Steene, L. Verloock, E. Tanghe, D. Plets, and W. Joseph, "50 Hz temporal magnetic field monitoring from high-voltage power lines: Sensor design and experimental validation," Sensors, vol. 24, no. 16, Art. no. 5325, 2024, doi: 10.3390/s24165325.

Details

Primary Language

English

Subjects

Health and Ecological Risk Assessment, Electrical Engineering (Other)

Journal Section

Research Article

Publication Date

September 30, 2026

Submission Date

February 12, 2026

Acceptance Date

July 21, 2026

Published in Issue

Year 2026 Number: 066

APA
Unsal, D. B. (2026). Environmental risk analysis of electromagnetic field levels in power lines for smart grid infrastructure. Journal of Scientific Reports-A, 066, 105-128. https://doi.org/10.59313/jsr-a.1888247
AMA
1.Unsal DB. Environmental risk analysis of electromagnetic field levels in power lines for smart grid infrastructure. JSR-A. 2026;(066):105-128. doi:10.59313/jsr-a.1888247
Chicago
Unsal, Derya Betul. 2026. “Environmental Risk Analysis of Electromagnetic Field Levels in Power Lines for Smart Grid Infrastructure”. Journal of Scientific Reports-A, nos. 066: 105-28. https://doi.org/10.59313/jsr-a.1888247.
EndNote
Unsal DB (September 1, 2026) Environmental risk analysis of electromagnetic field levels in power lines for smart grid infrastructure. Journal of Scientific Reports-A 066 105–128.
IEEE
[1]D. B. Unsal, “Environmental risk analysis of electromagnetic field levels in power lines for smart grid infrastructure”, JSR-A, no. 066, pp. 105–128, Sept. 2026, doi: 10.59313/jsr-a.1888247.
ISNAD
Unsal, Derya Betul. “Environmental Risk Analysis of Electromagnetic Field Levels in Power Lines for Smart Grid Infrastructure”. Journal of Scientific Reports-A. 066 (September 1, 2026): 105-128. https://doi.org/10.59313/jsr-a.1888247.
JAMA
1.Unsal DB. Environmental risk analysis of electromagnetic field levels in power lines for smart grid infrastructure. JSR-A. 2026;:105–128.
MLA
Unsal, Derya Betul. “Environmental Risk Analysis of Electromagnetic Field Levels in Power Lines for Smart Grid Infrastructure”. Journal of Scientific Reports-A, no. 066, Sept. 2026, pp. 105-28, doi:10.59313/jsr-a.1888247.
Vancouver
1.Derya Betul Unsal. Environmental risk analysis of electromagnetic field levels in power lines for smart grid infrastructure. JSR-A. 2026 Sep. 1;(066):105-28. doi:10.59313/jsr-a.1888247