Environmental risk analysis of electromagnetic field levels in power lines for smart grid infrastructure
Abstract
Smart grids bring more electrical equipment into cities, so the fields around this equipment need to be checked. Electric field strength (E) and magnetic flux density (B) in an underground transformer room, under a 380 kV, 50 Hz transmission line and near low and medium voltage distribution lines measured and expressed each reading as an exposure ratio (ER), i.e. as a percentage of the corresponding ICNIRP public reference level. The largest values were found 1 m above ground below the center conductor of the 380 kV line, where E was 1.396 kV/m (ER 27.9%) and B was 4.191 µT (ER 4.2%). For the same line, a three phase Biot–Savart expression came within about 4% of the measured B, while an ANSYS Maxwell model gave values 7%–21% above the analytical estimate over the current cases studied. On the risk scale adopted here, most locations fell into Category I or II. The transmission corridor was placed in Category III because of its electric field, even though no reading exceeded an ICNIRP reference level. The comparison also shows that the dominant field component differs between sources: E under the 380 kV line, B next to the transformer.
Keywords
Supporting Institution
Thanks
References
- [1] H. Kurt, "Risk analysis of electromagnetic field levels of transmission and distribution lines for smart grid infrastructure," M.S. thesis, Dept. Energy Sci. Technol. Eng., Sivas Cumhuriyet Univ., Sivas, Türkiye, 2023, pp. 75–79.
- [2] J. Park, E. Jeong, and G. Seomun, "Extremely low-frequency magnetic fields exposure measurement during lessons in elementary schools," Int. J. Environ. Res. Public Health, vol. 17, no. 15, Art. no. 5284, 2020, doi: 10.3390/ijerph17155284.
- [3] D. Baaken, D. Wollschläger, T. Samaras, J. Schüz, and I. Deltour, "Exposure to extremely low-frequency magnetic fields in low- and middle-income countries: An overview," Radiat. Prot. Dosim., vol. 191, no. 4, pp. 487–500, 2020, doi: 10.1093/rpd/ncaa172.
- [4] M. Landini, G. Mazzanti, and R. Mandrioli, "Procedure for verifying population exposure limits to the magnetic field from double-circuit overhead power lines," Electricity, vol. 2, no. 3, pp. 342–358, 2021, doi: 10.3390/electricity2030021.
- [5] L. S. Litzbarski et al., "The assessment of the influence of low-frequency electromagnetic fields originating from power infrastructure on human health," Appl. Sci., vol. 14, no. 21, Art. no. 9668, 2024, doi: 10.3390/app14219668.
- [6] H. Tian et al., "System-level biological effects of extremely low-frequency electromagnetic fields: An in vivo experimental review," Front. Neurosci., vol. 17, Art. no. 1247021, 2023, doi: 10.3389/fnins.2023.1247021.
- [7] Bilgi Teknolojileri ve İletişim Kurumu, "Ölçüm Takip Sistemi." [Online]. Available: https://www.btk.gov.tr/olcum-takip-sistemi (accessed Dec. 12, 2024).
- [8] K. Deprez, T. Van de Steene, L. Verloock, E. Tanghe, D. Plets, and W. Joseph, "50 Hz temporal magnetic field monitoring from high-voltage power lines: Sensor design and experimental validation," Sensors, vol. 24, no. 16, Art. no. 5325, 2024, doi: 10.3390/s24165325.
Details
Primary Language
English
Subjects
Health and Ecological Risk Assessment, Electrical Engineering (Other)
Journal Section
Research Article
Authors
Publication Date
September 30, 2026
Submission Date
February 12, 2026
Acceptance Date
July 21, 2026
Published in Issue
Year 2026 Number: 066