Conference Paper

Examination of Energy Efficiency of Air Handling Unit with Integrated Air to Air Heat Exchanger in Cooling Mode

Volume: 17 September 16, 2022
  • Slav Valchev
  • Ivan Mıhaılov
EN

Examination of Energy Efficiency of Air Handling Unit with Integrated Air to Air Heat Exchanger in Cooling Mode

Abstract

Object of the present study is an experimental determination of parameters, showing efficiency of air handling unit with integrated air to air heat exchanger in cooling mode: effectiveness of supply side of air to air heat exchanger, coefficient of performance and specific fan power of air handling unit. A daily performance of air handling unit in cooling mode is conducted. Effectiveness of supply side of air to air heat exchanger in range of 50.5 % to 74.3 % is received. Coefficient of performance in range of 0.88 to 2.99 and specific fan power of air handling unit in range of 1.77 kW/(m3/s) to 3.06 kW/(m3/s) are received. A relation between effectiveness of supply side of air to air heat exchanger and ratio of heat capacity rates of supply and exhaust air is received. Effectiveness of supply side of air to air heat exchanger depends on values of mass flow of supply and the exhaust air. High values of mass flow of exhaust air responds to high effectiveness of supply side of air to air heat exchanger.

Keywords

References

  1. Valchev, S.E. & Mihailov, I.M. (2022). Examination of energy efficiency of air handling unit with integrated air to air heat exchanger in cooling mode. The Eurasia Proceedings of Science, Technology, Engineering & Mathematics (EPSTEM), 17, 45-52.

Details

Primary Language

English

Subjects

Engineering

Journal Section

Conference Paper

Authors

Slav Valchev This is me
Bulgaria

Ivan Mıhaılov This is me
Bulgaria

Publication Date

September 16, 2022

Submission Date

August 10, 2022

Acceptance Date

August 15, 2022

Published in Issue

Year 2022 Volume: 17

APA
Valchev, S., & Mıhaılov, I. (2022). Examination of Energy Efficiency of Air Handling Unit with Integrated Air to Air Heat Exchanger in Cooling Mode. The Eurasia Proceedings of Science Technology Engineering and Mathematics, 17, 45-52. https://doi.org/10.55549/epstem.1175946