EXPERIMENTAL ASSESSMENT OF COMPARATIVE R290VS. R449A REFRIGERANTS BY USING 3E (ENERGY, EXERGY AND ENVIRONMENT) ANALYSIS: A SUPERMARKET APPLICATION

Volume: 7 Number: 3 March 1, 2021
  • Erhan Arslan
  • Meltem Kosan
  • Mustafa Aktas
  • Suleyman Erten
EN

EXPERIMENTAL ASSESSMENT OF COMPARATIVE R290VS. R449A REFRIGERANTS BY USING 3E (ENERGY, EXERGY AND ENVIRONMENT) ANALYSIS: A SUPERMARKET APPLICATION

Abstract

Efficiency is becoming an increasingly important issue in cooling systems. It is important to use micro channel heat exchangers in order to increase the cooling system efficiency. In this study, performance analysis of refrigerants used in supermarkets was tested experimentally. Thermodynamic analyses of the refrigerants were examined. The compatibility of R290 and R449A refrigerants with the environment has been experimentally observed. Energy, exergy, and environmental analyses were performed using R290 and R449a refrigerants based on the test results for 24 hours using double inlet and double outlet evaporator. Accordingly, in the experiments using R290, the exergy efficiency and COP value are 43.52 % and 2.09, respectively. In experiments using R449A, these values were found to be 22.28 % and 1.59. Exergy efficiency was increased by 48.81 % in experiments using propane. In addition, an increase of 24.12% was observed in the Coefficient of Performance (COP) value. Considering the environmental analysis results, the amount of CO2 emitted by the R290 refrigerant to the atmosphere during the test period was 3.14 kg/h and R449A was calculated as 3.97 kg/h. It was seen in this study that the R290 refrigerant emits 26.22 % less CO2 to the atmosphere.

Keywords

References

  1. [1] Protocol M. Montreal protocol on substances that deplete the ozone layer. Washington, DC: US Government Printing Office, 1987;26:128-136.
  2. [2] Low-Gwp A.O. Montreal Protocol On Substances That Deplete The Ozone Layer. 2019.
  3. [3] Schulz M. and D Kourkoulas. Regulation (EU) No 517/2014 of The European Parliament and of the council of 16 April 2014 on fluorinated greenhouse gases and repealing Regulation (EC) No 842/2006. Off. J. Eur. Union, 2014. 2014;(517):L150.
  4. [4] Ciconkov R. Refrigerants: There is still no vision for sustainable solutions. International Journal of Refrigeration 2018;86:441-448.
  5. [5] Heredia-Aricapa Y. et al. Overview of low GWP mixtures for the replacement of HFC refrigerants: R134a, R404A and R410A. International Journal of Refrigeration 2020;111:113-123.
  6. [6] He M.-G. et al. Application of natural refrigerant propane and propane/isobutane in large capacity chest freezer. Applied Thermal Engineering 2014;70(1):732-736.
  7. [7] Makhnatch P. et al. Retrofit of lower GWP alternative R449A into an existing R404A indirect supermarket refrigeration system. International Journal of Refrigeration 2017;76: 184-192.
  8. [8] Vaitkus L. and Dagilis V. Analysis of alternatives to high GWP refrigerants for eutectic refrigerating systems. International Journal of Refrigeration 2017;76:160-169.

Details

Primary Language

English

Subjects

Engineering

Journal Section

Research Article

Authors

Mustafa Aktas This is me
0000-0003-1187-5120
Türkiye

Suleyman Erten This is me
0000-0002-7811-6148
Türkiye

Publication Date

March 1, 2021

Submission Date

September 9, 2020

Acceptance Date

December 8, 2020

Published in Issue

Year 2021 Volume: 7 Number: 3

APA
Arslan, E., Kosan, M., Aktas, M., & Erten, S. (2021). EXPERIMENTAL ASSESSMENT OF COMPARATIVE R290VS. R449A REFRIGERANTS BY USING 3E (ENERGY, EXERGY AND ENVIRONMENT) ANALYSIS: A SUPERMARKET APPLICATION. Journal of Thermal Engineering, 7(3), 595-607. https://doi.org/10.18186/thermal.888449
AMA
1.Arslan E, Kosan M, Aktas M, Erten S. EXPERIMENTAL ASSESSMENT OF COMPARATIVE R290VS. R449A REFRIGERANTS BY USING 3E (ENERGY, EXERGY AND ENVIRONMENT) ANALYSIS: A SUPERMARKET APPLICATION. Journal of Thermal Engineering. 2021;7(3):595-607. doi:10.18186/thermal.888449
Chicago
Arslan, Erhan, Meltem Kosan, Mustafa Aktas, and Suleyman Erten. 2021. “EXPERIMENTAL ASSESSMENT OF COMPARATIVE R290VS. R449A REFRIGERANTS BY USING 3E (ENERGY, EXERGY AND ENVIRONMENT) ANALYSIS: A SUPERMARKET APPLICATION”. Journal of Thermal Engineering 7 (3): 595-607. https://doi.org/10.18186/thermal.888449.
EndNote
Arslan E, Kosan M, Aktas M, Erten S (March 1, 2021) EXPERIMENTAL ASSESSMENT OF COMPARATIVE R290VS. R449A REFRIGERANTS BY USING 3E (ENERGY, EXERGY AND ENVIRONMENT) ANALYSIS: A SUPERMARKET APPLICATION. Journal of Thermal Engineering 7 3 595–607.
IEEE
[1]E. Arslan, M. Kosan, M. Aktas, and S. Erten, “EXPERIMENTAL ASSESSMENT OF COMPARATIVE R290VS. R449A REFRIGERANTS BY USING 3E (ENERGY, EXERGY AND ENVIRONMENT) ANALYSIS: A SUPERMARKET APPLICATION”, Journal of Thermal Engineering, vol. 7, no. 3, pp. 595–607, Mar. 2021, doi: 10.18186/thermal.888449.
ISNAD
Arslan, Erhan - Kosan, Meltem - Aktas, Mustafa - Erten, Suleyman. “EXPERIMENTAL ASSESSMENT OF COMPARATIVE R290VS. R449A REFRIGERANTS BY USING 3E (ENERGY, EXERGY AND ENVIRONMENT) ANALYSIS: A SUPERMARKET APPLICATION”. Journal of Thermal Engineering 7/3 (March 1, 2021): 595-607. https://doi.org/10.18186/thermal.888449.
JAMA
1.Arslan E, Kosan M, Aktas M, Erten S. EXPERIMENTAL ASSESSMENT OF COMPARATIVE R290VS. R449A REFRIGERANTS BY USING 3E (ENERGY, EXERGY AND ENVIRONMENT) ANALYSIS: A SUPERMARKET APPLICATION. Journal of Thermal Engineering. 2021;7:595–607.
MLA
Arslan, Erhan, et al. “EXPERIMENTAL ASSESSMENT OF COMPARATIVE R290VS. R449A REFRIGERANTS BY USING 3E (ENERGY, EXERGY AND ENVIRONMENT) ANALYSIS: A SUPERMARKET APPLICATION”. Journal of Thermal Engineering, vol. 7, no. 3, Mar. 2021, pp. 595-07, doi:10.18186/thermal.888449.
Vancouver
1.Erhan Arslan, Meltem Kosan, Mustafa Aktas, Suleyman Erten. EXPERIMENTAL ASSESSMENT OF COMPARATIVE R290VS. R449A REFRIGERANTS BY USING 3E (ENERGY, EXERGY AND ENVIRONMENT) ANALYSIS: A SUPERMARKET APPLICATION. Journal of Thermal Engineering. 2021 Mar. 1;7(3):595-607. doi:10.18186/thermal.888449

Cited By

IMPORTANT NOTE: JOURNAL SUBMISSION LINK http://eds.yildiz.edu.tr/journal-of-thermal-engineering