Protection Coordination Practice in Electrical Substation Part-1 Overcurrent and Earth Fault Protection - Case Study of Siddik Kardesler Substation (SKS)

Volume: 30 Number: 4 December 11, 2017
EN

Protection Coordination Practice in Electrical Substation Part-1 Overcurrent and Earth Fault Protection - Case Study of Siddik Kardesler Substation (SKS)

Abstract

Protection coordination is the heart of all power systems. To insure a quality and reliable operation of the power systems, an electrical fault must be cleared within short time. This can be achieved by proper coordination between the protection relays. In Siddik Kardesler Substation the MV voltage feeders’ protection is provided by overcurrent relays. This paper is principally concerned with practical protection coordination of the electrical substation by using substation as case study. In the Part-2, distance and differential protection will be discussed. Finally, after test and commissioning, the substation is successfully energized without problem.

Keywords

References

  1. [1] Electric Power Engineering Handbook, Electrical Power Substation Engineering, edited by John D. McDonald, 2nd edition, 2007, Taylor & Francis Group, LLC.
  2. [2] Switch Gear and Substations, Siemens Energy Sector, Power Engineering Guide, Edition 7.
  3. [3] Raj Nagarsheth, Sushant Singh, Study of gas insulated substation and its comparison with air insulated substation, International Journal of Electrical Power and Energy Systems 55 (2014) 481–485.
  4. [4] IEEE Power Engineering Society, IEEE Guide for Recommended Electrical Clearances and Insulation Levels in Air-Insulated Electrical Power Substations, IEEE-SA Standards Board, and Approved 6 December 2006 accessed online on http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=4201973
  5. [5] Network Protection and Automation Guide, Protective Relays Measurement and Control, May, 2011, ISBN: 978-0-9568678-0-3 Published by Alstom Grid.
  6. [6] C.R. Bayliss, B.J. Hardy, Transmission and Distribution Electrical Engineering (Fourth Edition), 2012, Pages 93–119
  7. [7] Carlos A. Castillo Salazar, Arturo Conde Enríquez, Satu Elisa Schaeffer, Directional overcurrent relay coordination considering non-standardized time, Electric Power Systems Research,
  8. [8] Dr C.R. Bayliss, CEng FIET, B.J. Hardy, CEng FIET, Transmission and Distribution Electrical Engineering (Fourth Edition), 2012, Chapter 10 – Relay Protection Pages 287–359

Details

Primary Language

English

Subjects

Engineering

Journal Section

Research Article

Authors

Mehmet Rida Tur
MARDİN ARTUKLU ÜNİVERSİTESİ
Türkiye

Abdulfetah Shobole This is me
YILDIZ TEKNIK UNIV
Türkiye

Mustafa Baysal
YILDIZ TEKNIK UNIV
Türkiye

Mohammed Wadi This is me
YILDIZ TEKNIK UNIV
Türkiye

Publication Date

December 11, 2017

Submission Date

December 26, 2016

Acceptance Date

October 25, 2017

Published in Issue

Year 2017 Volume: 30 Number: 4

APA
Tur, M. R., Shobole, A., Baysal, M., & Wadi, M. (2017). Protection Coordination Practice in Electrical Substation Part-1 Overcurrent and Earth Fault Protection - Case Study of Siddik Kardesler Substation (SKS). Gazi University Journal of Science, 30(4), 180-198. https://izlik.org/JA39HH52ZD
AMA
1.Tur MR, Shobole A, Baysal M, Wadi M. Protection Coordination Practice in Electrical Substation Part-1 Overcurrent and Earth Fault Protection - Case Study of Siddik Kardesler Substation (SKS). Gazi University Journal of Science. 2017;30(4):180-198. https://izlik.org/JA39HH52ZD
Chicago
Tur, Mehmet Rida, Abdulfetah Shobole, Mustafa Baysal, and Mohammed Wadi. 2017. “Protection Coordination Practice in Electrical Substation Part-1 Overcurrent and Earth Fault Protection - Case Study of Siddik Kardesler Substation (SKS)”. Gazi University Journal of Science 30 (4): 180-98. https://izlik.org/JA39HH52ZD.
EndNote
Tur MR, Shobole A, Baysal M, Wadi M (December 1, 2017) Protection Coordination Practice in Electrical Substation Part-1 Overcurrent and Earth Fault Protection - Case Study of Siddik Kardesler Substation (SKS). Gazi University Journal of Science 30 4 180–198.
IEEE
[1]M. R. Tur, A. Shobole, M. Baysal, and M. Wadi, “Protection Coordination Practice in Electrical Substation Part-1 Overcurrent and Earth Fault Protection - Case Study of Siddik Kardesler Substation (SKS)”, Gazi University Journal of Science, vol. 30, no. 4, pp. 180–198, Dec. 2017, [Online]. Available: https://izlik.org/JA39HH52ZD
ISNAD
Tur, Mehmet Rida - Shobole, Abdulfetah - Baysal, Mustafa - Wadi, Mohammed. “Protection Coordination Practice in Electrical Substation Part-1 Overcurrent and Earth Fault Protection - Case Study of Siddik Kardesler Substation (SKS)”. Gazi University Journal of Science 30/4 (December 1, 2017): 180-198. https://izlik.org/JA39HH52ZD.
JAMA
1.Tur MR, Shobole A, Baysal M, Wadi M. Protection Coordination Practice in Electrical Substation Part-1 Overcurrent and Earth Fault Protection - Case Study of Siddik Kardesler Substation (SKS). Gazi University Journal of Science. 2017;30:180–198.
MLA
Tur, Mehmet Rida, et al. “Protection Coordination Practice in Electrical Substation Part-1 Overcurrent and Earth Fault Protection - Case Study of Siddik Kardesler Substation (SKS)”. Gazi University Journal of Science, vol. 30, no. 4, Dec. 2017, pp. 180-98, https://izlik.org/JA39HH52ZD.
Vancouver
1.Mehmet Rida Tur, Abdulfetah Shobole, Mustafa Baysal, Mohammed Wadi. Protection Coordination Practice in Electrical Substation Part-1 Overcurrent and Earth Fault Protection - Case Study of Siddik Kardesler Substation (SKS). Gazi University Journal of Science [Internet]. 2017 Dec. 1;30(4):180-98. Available from: https://izlik.org/JA39HH52ZD