Research Article

A single-phase solid-state fault current limiter: Simulation and experimental study

Volume: 42 Number: 1 February 27, 2024
EN

A single-phase solid-state fault current limiter: Simulation and experimental study

Abstract

Various methods are used to reduce fault currents in fault situations occurring in power sys-tems. In this study, a developed single-phase power electronics-based solid-state fault current limiter is presented. The proposed single-phase solid-state fault current limiter is designed as preliminary prototype of the three-phase low voltage solid-state fault current limiter. The maximum current and voltage capability of the fault current limiter is 16 A and 480 V. This limiter works according to the principle of series and parallel resonance. In normal operation, the current passes through the inductance and capacitor, which are in series resonance. Thus, extra voltage drops and power loss in the system are prevented. In the event of a fault, the lim-iter switches to parallel resonance, and its impedance increases. Therefore, the fault current is decreased. The developed circuit and control algorithm reduces the first peak of fault current with a rather high percentage by comparison with the fault current without fault current lim-iter. In addition, the amplitude of current oscillation is decreased, and the current is recovered in a short time because the control algorithm determines the fault start and end time fast. The effect of the limiter is demonstrated with the simulation results in Matlab/Simulink. The simu-lation results are verified with the application study carried out in the laboratory environment. The fault current reaches up to 58.5 A in case of fault current limiter is not used, whereas the developed fault current limiter suppresses the current to around 9 A. The value of maximum fault current decreases to 15% according to the non-fault current limiter used situation. In the study, detailed application notes of the limiter circuit are shared.

Keywords

References

  1. REFERENCES
  2. [1] Alawan MA. Design of intelligent distance relay for cascaded transmission line fault detection based on fuzzy logic system. Period Eng Nat Sci 2020;8:1075–1082.
  3. [2] Abdalı A, Abdalı K, Bagheri A. An elitist gravitational search algorithm based approach for optimal placement of fault current limiters in power systems. Sigma J Eng Nat Sci 2019;3:691–704.
  4. [3] Hussein AA, Ali MH. Comparison among series compensators for fault ride through capability enhancement of wind generator systems. Int J Renew Energy Res 2014;4:767–776.
  5. [4] Shobug MA, Sheikh MRI. Fault Management in DFIG Based Wind Turbine Using Sophisticated Advanced Solid State Fault Current Limiter. IEEE Region 10 Symposium (TENSYMP), Dhaka. 2020:1660–1663. [CrossRef]
  6. [5] Power AJ. An overview of transmission fault current limiters. IEE Colloquium on Fault Current Limiters – A Look at Tomorrow. London: IET Digital Library; 1995. [CrossRef]
  7. [6] Kraemer HP, Bauer A, Frank M, Hasselt PV, Kummeth P, Wohlfart M, et al. Assist- a superconducting fault current limiter in a public electric power grid. IEEE Trans Power Deliv 2022;37:612–618. [CrossRef]
  8. [7] Yadav S, Choudhary GK, Mandal RK. Review on fault current limiters. Int J Eng Res Technol 2014;3:1595–1603.

Details

Primary Language

English

Subjects

Structural Biology

Journal Section

Research Article

Publication Date

February 27, 2024

Submission Date

January 17, 2022

Acceptance Date

July 24, 2022

Published in Issue

Year 2024 Volume: 42 Number: 1

APA
Küçükaydın, B., İşen, E., & Arikan, O. (2024). A single-phase solid-state fault current limiter: Simulation and experimental study. Sigma Journal of Engineering and Natural Sciences, 42(1), 164-176. https://izlik.org/JA45WC89XD
AMA
1.Küçükaydın B, İşen E, Arikan O. A single-phase solid-state fault current limiter: Simulation and experimental study. SIGMA. 2024;42(1):164-176. https://izlik.org/JA45WC89XD
Chicago
Küçükaydın, Barış, Evren İşen, and Oktay Arikan. 2024. “A Single-Phase Solid-State Fault Current Limiter: Simulation and Experimental Study”. Sigma Journal of Engineering and Natural Sciences 42 (1): 164-76. https://izlik.org/JA45WC89XD.
EndNote
Küçükaydın B, İşen E, Arikan O (February 1, 2024) A single-phase solid-state fault current limiter: Simulation and experimental study. Sigma Journal of Engineering and Natural Sciences 42 1 164–176.
IEEE
[1]B. Küçükaydın, E. İşen, and O. Arikan, “A single-phase solid-state fault current limiter: Simulation and experimental study”, SIGMA, vol. 42, no. 1, pp. 164–176, Feb. 2024, [Online]. Available: https://izlik.org/JA45WC89XD
ISNAD
Küçükaydın, Barış - İşen, Evren - Arikan, Oktay. “A Single-Phase Solid-State Fault Current Limiter: Simulation and Experimental Study”. Sigma Journal of Engineering and Natural Sciences 42/1 (February 1, 2024): 164-176. https://izlik.org/JA45WC89XD.
JAMA
1.Küçükaydın B, İşen E, Arikan O. A single-phase solid-state fault current limiter: Simulation and experimental study. SIGMA. 2024;42:164–176.
MLA
Küçükaydın, Barış, et al. “A Single-Phase Solid-State Fault Current Limiter: Simulation and Experimental Study”. Sigma Journal of Engineering and Natural Sciences, vol. 42, no. 1, Feb. 2024, pp. 164-76, https://izlik.org/JA45WC89XD.
Vancouver
1.Barış Küçükaydın, Evren İşen, Oktay Arikan. A single-phase solid-state fault current limiter: Simulation and experimental study. SIGMA [Internet]. 2024 Feb. 1;42(1):164-76. Available from: https://izlik.org/JA45WC89XD

IMPORTANT NOTE: JOURNAL SUBMISSION LINK https://eds.yildiz.edu.tr/sigma/