Performance and Economic Analysis of a Variable Refrigerant Flow (VRF) System
Öz
This study deals with the exergetic modeling and performance/cost evaluation of a variable refrigerant flow (VRF) air conditioning system. An experimental setup was established to investigate the system performance under cooling conditions. System mainly consists of one outdoor unit and two indoor units. Outdoor unit equipped with two compressors (one variable speed and one constant speed), condenser, and four way valve is connected to two indoor units. Exergy, cost, energy and mass (EXCEM) analysis was applied to this system for the first time to the best of the authors` knowledge. The relations between thermodynamic losses and capital costs were also parametrically investigated. Experimental results show that the greatest irreversibility (exergy destruction) occurs in the condenser, followed by the evaporators. Exergy efficiency of the whole system on the exergetic product/fuel basis was calculated to be 85.84% at a reference state temperature of 25 oC. Exergy efficiency and exergy loss rate were in the range of 85.27-86.55% and 0.919-0.916 MW/USD, respectively, based upon the conditions and parameters considered in the present study.
Anahtar Kelimeler
Kaynakça
- 1. Huang, W.Z., Zaheeruddin, M., Cho, S.H., 2006. Dynamic Simulation of Energy Management Control Functions for HVAC Systems in Buildings, Energy Conversion and Management 47 (7–8), 926-943.
- 2. International Energy Agency (IEA), World Energy Outlook, OECD/IEA, France, 2012. www.worldenergyoutlook.org/publications/weo-2012/.
- 3. Ürge-Vorsatz, D., Cabeza, L., Serrano, S., Barreneche C., Petrichenko, K., 2015. Heating and Cooling Energy Trends and Drivers in Buildings, Renewable and Sustainable Energy Reviews 41, 85-98.
- 4. Goetzler, W., 2007. Variable Refrigerant Flow Systems, ASHRAE Journal 49 (4), 24-31.
- 5. Aynur, T.N., Hwang, Y., Radermacher, R., 2008a. Experimental Evaluation of the Ventilation Effect on the Performance of a VRV System in Cooling Mode-Part I: Experimental evaluation, HVAC&R Research, Vol.14, No.4, 615-630.
- 6. Aynur, T.N., Hwang, Y., Radermacher, R., 2008b. Simulation Evaluation of the Ventilation Effect on the Performance of a VRV System in Cooling Mode—Part II: Simulation Evaluation. HVAC&R Research, Vol. 14, No. 5, 783-795.
- 7. Aynur, T.N., 2010. Variable Refrigerant Flow Systems: A review, Energy and Buildings 42: 1106-1112.
- 8. Jain, N., Koelna, J., Sundaramb, S., Alleynea, A., 2014. Partially Decentralized Control of Large-scale Variable-Refrigerant-Flowsystems in Buildings, Journal of Process Control 24, 798-819.
Ayrıntılar
Birincil Dil
Türkçe
Konular
-
Bölüm
Araştırma Makalesi
Yazarlar
Ertaç Hürdoğan
*
OSMANİYE KORKUT ATA ÜNİVERSİTESİ, MÜHENDİSLİK FAKÜLTESİ, ENERJİ SİSTEMLERİ MÜHENDİSLİĞİ BÖLÜMÜ
Türkiye
Alper Yıldırım
Bu kişi benim
OSMANİYE KORKUT ATA ÜNİVERSİTESİ, OSMANİYE MESLEK YÜKSEKOKULU, MAKİNE VE METAL TEKNOLOJİLERİ BÖLÜMÜ
Türkiye
Coşkun Özalp
Bu kişi benim
OSMANİYE KORKUT ATA ÜNİVERSİTESİ, MÜHENDİSLİK FAKÜLTESİ, ENERJİ SİSTEMLERİ MÜHENDİSLİĞİ BÖLÜMÜ
Türkiye
Yayımlanma Tarihi
15 Eylül 2017
Gönderilme Tarihi
4 Mayıs 2017
Kabul Tarihi
26 Eylül 2017
Yayımlandığı Sayı
Yıl 2017 Cilt: 32 Sayı: 3