Research Article

Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler

Volume: 10 Number: 1 March 30, 2022
EN

Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler

Abstract

In this study, an innovative indirect evaporative cooler is presented and experimentally analysed. A prototype was assembled for the experimental investigation of the system and tested in the laboratory environment under the conditions of constant air flow rate of 350 m3/h, circulating water temperatures of 15°C and 20°C, inlet air temperatures of 25°C and 30°C and lastly inlet air humidity of 9g/kg and 13g/kg, respectively. Based on the data obtained during the experiments, calculations were performed for the cooling capacity, cooling efficiency, energy efficiency and exergy efficiency of the system for each case. The findings showed that the highest wet bulb efficiency, dew point efficiency and EER of evaporative cooler were found to be 0.91, 0.62, and 0.77, respectively.

Keywords

Supporting Institution

Necmettin Erbakan Üniversitesi

Project Number

201216001

Thanks

The authors gratefully acknowledge the financial support of Scientific Research Council (BAP) of the Necmettin Erbakan University (Project no: 201216001).

References

  1. [1] Duan, Z., Zhan, C., Zhang, X., Mustafa, M., Zhao, X., Alimohammadisagvand, B., & Hasan, A. (2012). Indirect evaporative cooling: Past, present and future potentials. Renewable and Sustainable Energy Reviews, 16(9), 6823-6850.
  2. [2] Buker, Mahmut Sami; Riffat, Saffa B. Recent developments in solar assisted liquid desiccant evaporative cooling technology—A review. Energy and Buildings, 2015, 96: 95-108.
  3. [3] Yang, Y., Cui, G., & Lan, C. Q. (2019). Developments in evaporative cooling and enhanced evaporative cooling-A review. Renewable and Sustainable Energy Reviews, 113, 109230.
  4. [4] Yang, H., Shi, W., Chen, Y., & Min, Y. (2021). Research development of indirect evaporative cooling technology: An updated review. Renewable and Sustainable Energy Reviews, 145, 111082.
  5. [5] Buker, Mahmut Sami; Mempouo, Blaise; Riffat, Saffa B. Experimental investigation of a building integrated photovoltaic/thermal roof collector combined with a liquid desiccant enhanced indirect evaporative cooling system. Energy Conversion and Management, 2015, 101: 239-254.
  6. [6] Bom, G. J., Foster, R., Dijkstra, E., Tummers, M., Evaporative air-conditioning: applications for environmentally friendly cooling, The World Bank, 1999
  7. [7] Osma E., Evaporatif Soğutma Sistemlerinin Mekanik Buhar Sıkıştırmalı Soğutma Sistemleri İle Termodinamik Ve Ekonomik Bakımdan Karşılaştırılması, Yüksek Lisans Tezi, Namık Kemal Üniversitesi Fen Bilimleri Enstitüsü, Tekirdağ, 2011.
  8. [8] El-Refaie, M. F., Kaseb, S., Speculation in the feasibility of evaporative cooling, Building and Environment, 2009, 44(4): 826-838.

Details

Primary Language

English

Subjects

Engineering

Journal Section

Research Article

Publication Date

March 30, 2022

Submission Date

December 16, 2021

Acceptance Date

February 13, 2022

Published in Issue

Year 2022 Volume: 10 Number: 1

APA
Özden, E., & Büker, M. S. (2022). Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler. Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım Ve Teknoloji, 10(1), 103-117. https://doi.org/10.29109/gujsc.1037675
AMA
1.Özden E, Büker MS. Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler. GUJS Part C. 2022;10(1):103-117. doi:10.29109/gujsc.1037675
Chicago
Özden, Ekrem, and Mahmut Sami Büker. 2022. “Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler”. Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım Ve Teknoloji 10 (1): 103-17. https://doi.org/10.29109/gujsc.1037675.
EndNote
Özden E, Büker MS (March 1, 2022) Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler. Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım ve Teknoloji 10 1 103–117.
IEEE
[1]E. Özden and M. S. Büker, “Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler”, GUJS Part C, vol. 10, no. 1, pp. 103–117, Mar. 2022, doi: 10.29109/gujsc.1037675.
ISNAD
Özden, Ekrem - Büker, Mahmut Sami. “Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler”. Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım ve Teknoloji 10/1 (March 1, 2022): 103-117. https://doi.org/10.29109/gujsc.1037675.
JAMA
1.Özden E, Büker MS. Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler. GUJS Part C. 2022;10:103–117.
MLA
Özden, Ekrem, and Mahmut Sami Büker. “Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler”. Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım Ve Teknoloji, vol. 10, no. 1, Mar. 2022, pp. 103-17, doi:10.29109/gujsc.1037675.
Vancouver
1.Ekrem Özden, Mahmut Sami Büker. Experimental Investigation on the Cooling Performance of a Counterflow Dew Point Evaporative Cooler. GUJS Part C. 2022 Mar. 1;10(1):103-17. doi:10.29109/gujsc.1037675

                                TRINDEX     16167        16166    21432    logo.png

      