BibTex RIS Cite

-

Year 2015, Volume: 19 Issue: 1, - , 31.01.2015

Abstract

The aım of this study is the calculation of the pipe diameter required to transfer the oil in the vertical parts of the cooling systems, at the desired cooling load and at the velocity of the minimum cooling liquid. For this purpose, the velocity of the minimum cooling liquid for the driftage of the oil in the pipes in the suction line (Vs,min) and the minimum cooling load (qs,min) have been studied. After the theoretical analysis as to the matter, in a system the cooling load of which 1 kW, for the copper pipes whose types are K and L, in place of the cooling liquids harming the ozon layer and leading to global warming, the environment-friendly, natural and alternative liquids R134A, R410A, R423A and R744 have been used. According to the results, as the pipe diameters increase, the velocity of minimum cooling liquid for the driftage of the oil increases. In addition to that, the load of the minimum cooling liquid increases, both the pipe diameters and the heat of the evaporator being increased. Cooling liquids being considered, the change of the velocities as R744

References

  • Callaghan, P., Vainio, M., 2003, EC poised for action on
  • HFC134a in MACs: Results of MAC summit 2003,
  • Earth Technology Forum, Motor Vehicle A/C Regulatory Innovations, Washington. Cremaschi, L., Hwang, Y., Radermacher R., 2005,
  • Experimental investigation of oil retention in air conditioning systems, International Journal of Refrigeration, 28, 1018 – 1028.
  • Çengel, Y.A., Cimbala, J.M., 2008, Akışkanlar Mekaniği
  • Temelleri ve Uygulamaları, Güven Bilimsel Yayınevi (Birinci Baskı), 938s, İzmir. Dincer I. 2003, Refrigeration System and Applications. Wiley:West Sussex.
  • Eryiğit, M., 2010, Yeni Nesil Soğutucu Akışkanlarda
  • Boru Çapı Hesabı, Süleyman Demirel Üniversitesi, Fen Bilimleri Enstitüsü Yüksek Lisans Tezi, 99s, Isparta. Fox, W.R., Mcdonald, T. A., 1992, Introduction To
  • Fluid Mechanics, John Wiley and Sons, Inc. (Fourth Edition), New York. Garland NP, Hadfield, M., 2005, Environmental implications of hydrocarbon refrigerants applied to the hermetic compressor, Materials and Design, 26, 578–586.
  • Hwang, Y., Lee J. P., Radermacher R., 2007, Oil distribution in a transcritical CO2 air-conditioning system, Applied Thermal Engineering, 27, 2618– 26
  • Kesim, S.C., Albayrak, K., İleri, A., 1999, Oil entrainment in
  • International Journal of Refrigeration, 23, 626-631. refrigerant piping, Klein SA. 2013 Engineering equation solver (EES),
  • Version 9.433. F-Chart Software. Koyun, T., Koyun, A., Acar, M., 2005, Soğutma
  • Sistemlerinde Kullanılan Soğutucu Akışkanlar ve Bu Akışkanların Ozon Tabakası Üzerine Etkileri, Tesisat Mühendisliği Dergisi, 88, 46-53. Lee J. P., 2003, Experimental and Theoretical
  • Investigation of Oil Retention in a Carbon Dioxide Air- Conditioning System, Doctora Thesis, University of Maryland. Sethi, A., 2011, Oil Retention and Pressure Drop of
  • R1234yf and R134a wıth POE ISO 32 in Suction Lines,
  • Master Thesis, University of Illinois at Urbana – Champaign. Tritton, D.J., 1998, Physical Fluid Dynamics,
  • Clarendon Press, (Second Edition), Oxford. White, F. M., 2004, Akışkanlar Mekaniği, Literatür yayınları: 110 (Birinci Baskı), İstanbul.
  • Zoellick, K., Hrnjak, P., 2010, Oil Retention and Pressure Drop in Horizontal and Vertical Suction
  • Lines with R410A/POE, International Refrigeration and Air Conditioning Conference, page 2327. Semboller A Di g hb hs R Re T P Uyağ(y) Q ΔP W e
  • Vyağ,min Yağın aşağı akmasını önlemek için ara yüzdeki minimum yağ hızı Vs,min soğutucu akışkan hızı qs,min μ ρ ν Kinematik viskozite

Boru Çapının Soğutucu Akışkan Hızına ve Soğutma Yüküne Etkisi

Year 2015, Volume: 19 Issue: 1, - , 31.01.2015

Abstract

Bu çalışmanın amacı, soğutma sistemlerinin dikey bölümlerinde bulunan yağın, istenilen soğutma yükünde ve en az soğutucu akışkan hızıyla taşınabilmesi için gerekli boru çapının hesaplanmasıdır. Bu amaçla, emiş hattında bulunan borulardaki yağın sürüklenebilmesi için gerekli olan minimum soğutucu akışkan hızının (V_(s,min)) ve minimum soğutma yükünün (q_(s,min)) boru çapına göre değişimi incelenmiştir. Konuyla ilgili teorik analizler yapıldıktan sonra, soğutma yükünün 1 kW olduğu bir sistemde K ve L tipi bakır borular için ozon tabakasına zarar veren ve küresel ısınmaya yol açan soğutucu akışkanların yerine çevre dostu doğal ve alternatif akışkanlardan R134A, R410A, R423A ve R744 soğutucu akışkanlar kullanılmıştır. Sonuçlara göre boru çaplarının artmasıyla yağın sürüklenebilmesi için gereken minimum soğutucu akışkan hızı da artmaktadır. Ayrıca hem boru çaplarının arttırılması hem de evaporatör sıcaklığındaki artış ile minimum soğutucu yükünde artış meydana gelmiştir. Soğutucu akışkanlar dikkate alındığında hızlardaki değişim R744

References

  • Callaghan, P., Vainio, M., 2003, EC poised for action on
  • HFC134a in MACs: Results of MAC summit 2003,
  • Earth Technology Forum, Motor Vehicle A/C Regulatory Innovations, Washington. Cremaschi, L., Hwang, Y., Radermacher R., 2005,
  • Experimental investigation of oil retention in air conditioning systems, International Journal of Refrigeration, 28, 1018 – 1028.
  • Çengel, Y.A., Cimbala, J.M., 2008, Akışkanlar Mekaniği
  • Temelleri ve Uygulamaları, Güven Bilimsel Yayınevi (Birinci Baskı), 938s, İzmir. Dincer I. 2003, Refrigeration System and Applications. Wiley:West Sussex.
  • Eryiğit, M., 2010, Yeni Nesil Soğutucu Akışkanlarda
  • Boru Çapı Hesabı, Süleyman Demirel Üniversitesi, Fen Bilimleri Enstitüsü Yüksek Lisans Tezi, 99s, Isparta. Fox, W.R., Mcdonald, T. A., 1992, Introduction To
  • Fluid Mechanics, John Wiley and Sons, Inc. (Fourth Edition), New York. Garland NP, Hadfield, M., 2005, Environmental implications of hydrocarbon refrigerants applied to the hermetic compressor, Materials and Design, 26, 578–586.
  • Hwang, Y., Lee J. P., Radermacher R., 2007, Oil distribution in a transcritical CO2 air-conditioning system, Applied Thermal Engineering, 27, 2618– 26
  • Kesim, S.C., Albayrak, K., İleri, A., 1999, Oil entrainment in
  • International Journal of Refrigeration, 23, 626-631. refrigerant piping, Klein SA. 2013 Engineering equation solver (EES),
  • Version 9.433. F-Chart Software. Koyun, T., Koyun, A., Acar, M., 2005, Soğutma
  • Sistemlerinde Kullanılan Soğutucu Akışkanlar ve Bu Akışkanların Ozon Tabakası Üzerine Etkileri, Tesisat Mühendisliği Dergisi, 88, 46-53. Lee J. P., 2003, Experimental and Theoretical
  • Investigation of Oil Retention in a Carbon Dioxide Air- Conditioning System, Doctora Thesis, University of Maryland. Sethi, A., 2011, Oil Retention and Pressure Drop of
  • R1234yf and R134a wıth POE ISO 32 in Suction Lines,
  • Master Thesis, University of Illinois at Urbana – Champaign. Tritton, D.J., 1998, Physical Fluid Dynamics,
  • Clarendon Press, (Second Edition), Oxford. White, F. M., 2004, Akışkanlar Mekaniği, Literatür yayınları: 110 (Birinci Baskı), İstanbul.
  • Zoellick, K., Hrnjak, P., 2010, Oil Retention and Pressure Drop in Horizontal and Vertical Suction
  • Lines with R410A/POE, International Refrigeration and Air Conditioning Conference, page 2327. Semboller A Di g hb hs R Re T P Uyağ(y) Q ΔP W e
  • Vyağ,min Yağın aşağı akmasını önlemek için ara yüzdeki minimum yağ hızı Vs,min soğutucu akışkan hızı qs,min μ ρ ν Kinematik viskozite
There are 21 citations in total.

Details

Primary Language Turkish
Journal Section MÜHENDİSLİK ve MİMARLIK BİLİMLERİ
Authors

Murat Eryiğit This is me

Mustafa Usal

Ahmet Kabul

Publication Date January 31, 2015
Published in Issue Year 2015 Volume: 19 Issue: 1

Cite

APA Eryiğit, M., Usal, M., & Kabul, A. (2015). Boru Çapının Soğutucu Akışkan Hızına ve Soğutma Yüküne Etkisi. Süleyman Demirel Üniversitesi Fen Bilimleri Enstitüsü Dergisi, 19(1). https://doi.org/10.19113/sdufbed.14410
AMA Eryiğit M, Usal M, Kabul A. Boru Çapının Soğutucu Akışkan Hızına ve Soğutma Yüküne Etkisi. J. Nat. Appl. Sci. April 2015;19(1). doi:10.19113/sdufbed.14410
Chicago Eryiğit, Murat, Mustafa Usal, and Ahmet Kabul. “Boru Çapının Soğutucu Akışkan Hızına Ve Soğutma Yüküne Etkisi”. Süleyman Demirel Üniversitesi Fen Bilimleri Enstitüsü Dergisi 19, no. 1 (April 2015). https://doi.org/10.19113/sdufbed.14410.
EndNote Eryiğit M, Usal M, Kabul A (April 1, 2015) Boru Çapının Soğutucu Akışkan Hızına ve Soğutma Yüküne Etkisi. Süleyman Demirel Üniversitesi Fen Bilimleri Enstitüsü Dergisi 19 1
IEEE M. Eryiğit, M. Usal, and A. Kabul, “Boru Çapının Soğutucu Akışkan Hızına ve Soğutma Yüküne Etkisi”, J. Nat. Appl. Sci., vol. 19, no. 1, 2015, doi: 10.19113/sdufbed.14410.
ISNAD Eryiğit, Murat et al. “Boru Çapının Soğutucu Akışkan Hızına Ve Soğutma Yüküne Etkisi”. Süleyman Demirel Üniversitesi Fen Bilimleri Enstitüsü Dergisi 19/1 (April 2015). https://doi.org/10.19113/sdufbed.14410.
JAMA Eryiğit M, Usal M, Kabul A. Boru Çapının Soğutucu Akışkan Hızına ve Soğutma Yüküne Etkisi. J. Nat. Appl. Sci. 2015;19. doi:10.19113/sdufbed.14410.
MLA Eryiğit, Murat et al. “Boru Çapının Soğutucu Akışkan Hızına Ve Soğutma Yüküne Etkisi”. Süleyman Demirel Üniversitesi Fen Bilimleri Enstitüsü Dergisi, vol. 19, no. 1, 2015, doi:10.19113/sdufbed.14410.
Vancouver Eryiğit M, Usal M, Kabul A. Boru Çapının Soğutucu Akışkan Hızına ve Soğutma Yüküne Etkisi. J. Nat. Appl. Sci. 2015;19(1).

e-ISSN :1308-6529
Linking ISSN (ISSN-L): 1300-7688

All published articles in the journal can be accessed free of charge and are open access under the Creative Commons CC BY-NC (Attribution-NonCommercial) license. All authors and other journal users are deemed to have accepted this situation. Click here to access detailed information about the CC BY-NC license.