Experimental Investigation of the Effects of IEC 61439-2 Separation Forms on Production Time and Cost in Low-Voltage Switchgear and Controlgear Assemblies
Öz
Separation forms used in low-voltage switchgear and controlgear assemblies provide mechanical segregation between busbar systems, functional units, and terminal connections, thereby contributing to personnel safety, operational continuity, and ease of maintenance. In this study, the effects of Form 1, Form 2A, Form 2B, Form 3A, Form 3B, Form 4A, and Form 4B separation forms defined in IEC 61439-2 on production time and production cost were experimentally investigated under actual manufacturing conditions. A single prototype assembly based on the same electrical design was used throughout the study. The electrical design, manufacturing environment, and assembly team were kept constant, while environmental conditions were maintained within comparable ranges, and the prototype was sequentially converted into different separation forms. Each manufacturing operation was performed once, and operation times were determined from video recordings. For Form 1, the total production time and total production cost were calculated as 327 min and €2968.51, respectively, whereas these values increased to 973 min and €5210.90 for Form 4B. Accordingly, compared with Form 1, the production time of Form 4B increased by 197.6%, while the total production cost increased by 75.5%. However, although production time generally increased with increasing separation level, production cost did not follow the same trend. The total production cost decreased by 4.9% from Form 2B to Form 3A and by 9.1% from Form 3B to Form 4A. These differences were mainly associated with variations in separation components, busbar quantities, circuit breaker and cable cassettes, and other mechanical components required by each separation form. The results demonstrate that production time and production cost represent distinct parameters that should nevertheless be evaluated jointly when selecting a separation form. The findings also indicate that assuming a fixed increase in production cost solely on the basis of the separation level may lead to inaccurate assessments during manufacturing. Since the contribution of the present findings is limited to the prototype and manufacturing conditions investigated in this study, further studies involving different switchgear configurations and manufacturing practices are required to broaden the empirical evidence available in the literature.
Anahtar Kelimeler
- IEC 61439
- LV switchgear assemblies
- Separation forms
- Switchgear manufacturing processes
- Production cost analysis
Etik Beyan
Ethics committee approval was not required because this study did not involve human participants or animals.
Teşekkür
This article was produced from the master's thesis of Hasan Metin conducted under the supervision of Murat Fidan. The authors would like to thank Prosis Elektrik for providing access to its low-voltage switchgear manufacturing facility and for its support during the experimental study.
Kaynakça
- Arias Velasquez, R. M. (2022). Influence of string-box size and the derating factor associated to the DC protection for PV solar panels. Electric Power Systems Research, 209, 107992. https://doi.org/10.1016/j.epsr.2022.107992
- Będkowski, M., Smołka, J., Banasiak, K., Buliński, Z., Nowak, A. J., Tomanek, T., & Wajda, A. (2014). Coupled numerical modelling of power loss generation in busbar system of low-voltage switchgear. International Journal of Thermal Sciences, 82, 122–129. https://doi.org/10.1016/j.ijthermalsci.2014.04.001
- Będkowski, M., Smołka, J., Buliński, Z., & Ryfa, A. (2017). Simulation of cooling enhancement in industrial low-voltage switchgear using validated coupled CFD–EMAG model. International Journal of Thermal Sciences, 111, 437–449. https://doi.org/10.1016/j.ijthermalsci.2016.09.025
- Berhausen, S., & Burzynski, R. (2025). Controlling the effects of an internal arc fault and benefits of active arc protection in low-voltage switchgear assemblies. IEEE Access, 13, 46887–46896. https://doi.org/10.1109/ACCESS.2025.3550847
- Bouman, B., & Muileboom, A. (2009). Essential changes in the product standard for low voltage MCC and switchgear. 2009 Conference Record PCIC Europe (pp. 64–69).
- Bründl, P., Stoidner, M., Bredthauer, J., Nguyen, H. G., Baechler, A., & Franke, J. (2024b). Unlocking the potential of digitalization and automation: A qualitative and quantitative study of the control cabinet manufacturing industry. Production & Manufacturing Research, 12(1), 2306820. https://doi.org/10.1080/21693277.2024.2306820
- Bründl, P., Stoidner, M., Nguyen, H. G., Abrass, A., & Franke, J. (2024a). Optimizing intralogistics in an engineer-to-order enterprise with job shop production: A case study of the control cabinet manufacturing. SAE International Journal of Materials and Manufacturing, 17(1), 05-17-01-0006. https://doi.org/10.4271/05-17-01-0006
- Delgado, F., Renedo, C. J., Ortiz, A., Fernández, I., & Santisteban, A. (2017). 3D thermal model and experimental validation of a low voltage three-phase busduct. Applied Thermal Engineering, 110, 1643–1652. https://doi.org/10.1016/j.applthermaleng.2016.09.002
Ayrıntılar
Birincil Dil
İngilizce
Konular
Elektrik Mühendisliği (Diğer)
Bölüm
Araştırma Makalesi
Yayımlanma Tarihi
15 Kasım 2026
Gönderilme Tarihi
26 Ağustos 2026
Kabul Tarihi
8 Ekim 2026
Yayımlandığı Sayı
Yıl 2026 Cilt: 9 Sayı: 6
APA
Metin, H., & Fidan, M. (2026). Experimental Investigation of the Effects of IEC 61439-2 Separation Forms on Production Time and Cost in Low-Voltage Switchgear and Controlgear Assemblies. Black Sea Journal of Engineering and Science, 9(6), 3390-3406. https://doi.org/10.34248/bsengineering.2026182
AMA
1.Metin H, Fidan M. Experimental Investigation of the Effects of IEC 61439-2 Separation Forms on Production Time and Cost in Low-Voltage Switchgear and Controlgear Assemblies. BSJ Eng. Sci. 2026;9(6):3390-3406. doi:10.34248/bsengineering.2026182
Chicago
Metin, Hasan, ve Murat Fidan. 2026. “Experimental Investigation of the Effects of IEC 61439-2 Separation Forms on Production Time and Cost in Low-Voltage Switchgear and Controlgear Assemblies”. Black Sea Journal of Engineering and Science 9 (6): 3390-3406. https://doi.org/10.34248/bsengineering.2026182.
EndNote
Metin H, Fidan M (15 Kasım 2026) Experimental Investigation of the Effects of IEC 61439-2 Separation Forms on Production Time and Cost in Low-Voltage Switchgear and Controlgear Assemblies. Black Sea Journal of Engineering and Science 9 6 3390–3406.
IEEE
[1]H. Metin ve M. Fidan, “Experimental Investigation of the Effects of IEC 61439-2 Separation Forms on Production Time and Cost in Low-Voltage Switchgear and Controlgear Assemblies”, BSJ Eng. Sci., c. 9, sy 6, ss. 3390–3406, Kas. 2026, doi: 10.34248/bsengineering.2026182.
ISNAD
Metin, Hasan - Fidan, Murat. “Experimental Investigation of the Effects of IEC 61439-2 Separation Forms on Production Time and Cost in Low-Voltage Switchgear and Controlgear Assemblies”. Black Sea Journal of Engineering and Science 9/6 (15 Kasım 2026): 3390-3406. https://doi.org/10.34248/bsengineering.2026182.
JAMA
1.Metin H, Fidan M. Experimental Investigation of the Effects of IEC 61439-2 Separation Forms on Production Time and Cost in Low-Voltage Switchgear and Controlgear Assemblies. BSJ Eng. Sci. 2026;9:3390–3406.
MLA
Metin, Hasan, ve Murat Fidan. “Experimental Investigation of the Effects of IEC 61439-2 Separation Forms on Production Time and Cost in Low-Voltage Switchgear and Controlgear Assemblies”. Black Sea Journal of Engineering and Science, c. 9, sy 6, Kasım 2026, ss. 3390-06, doi:10.34248/bsengineering.2026182.
Vancouver
1.Hasan Metin, Murat Fidan. Experimental Investigation of the Effects of IEC 61439-2 Separation Forms on Production Time and Cost in Low-Voltage Switchgear and Controlgear Assemblies. BSJ Eng. Sci. 15 Kasım 2026;9(6):3390-406. doi:10.34248/bsengineering.2026182