Öz
In this study, the economical and exergoeconomik analysis of the central heating system which produces a total of 20 tons/hour of steam was conducted in in the Van Yüzüncü Yıl University campus. As a result of the analysis, the total energy efficiency of the boilers, which is the most important part of the system, was found to be 90% and the exergy efficiency as 31%. The exergetic efficiency of the whole system was found to be 29%. As a result of the exergoeconomic analysis, the annual fuel consumption cost of the system, the annual product cost price, the unit exergy cost of the parameters entering and leaving the system were calculated. As a result of the calculations, the hourly cost of the product was found to be: 291.78 $/h, the hourly cost of fuel: 252.30 $/h.