The Alternative Methods for Recovery of Condensed Water in Air Handling Systems

Yıl 2018, , 893 - 901, 01.08.2018
https://doi.org/10.29130/dubited.432814

Öz

The most important parts of central heating and cooling systems are air handling units. In the air handling units, large amounts of water condense from the cooling coil and this water is usually given to the waste water line. In practice this water is described as a major waste. Whereas, this cold water in systems operating with 100% outside air can be stored and it can be evaluated in many applications including evaporative cooling. In this study, different designs were proposed for the recovery of condensed water in air handling units. Studies have
been carried out on three different systems. In the first system, the using of the condensed water obtained from the 100 % fresh air handling units as a precooler in a coil of an air-handling unit with a mixture air was investigated. In the second system, the condensing water in the cooling coil of the 100% fresh air or mixed air handling unit was investigated as feeding water in a chiller device with cooling tower. In the third system, the using of the water, which was condensed in the 100% fresh-air or mixed air handling units, in the chiller device with air cooled condenser was examined. Psychrometric calculations show that a latent heat of about 80 kW in an air conditioning unit operating with 100% fresh air can be used as sensible heat through these designed systems.

Kaynakça

  • [1] Guo, Y., Tan, Z., Chen, H., Li, G., Wang, J., Huang, R., ... & Ahmad, T, “Deep learning-based fault diagnosis of variable refrigerant flow air-conditioning system for building energy saving”, Applied Energy, 225., 732-745., 2018.
  • [2] Hong T, Koo C, Kim J, Lee M, Jeong K, “A review on sustainable construction management strategies for monitoring, diagnosing, and retrofitting the building’s dynamic energy performance: focused on the operation and maintenance phase”, Applied Energy, 155., 671–707., 2015.
  • [3] Yang, L., Yan, H., & Lam, J. C, “Thermal comfort and building energy consumption implications–a review”, Applied Energy, 115., 164-173., 2014.
  • [4] “Türkiye enerji verimliliği gelişim raporu” Yenilenebilir Enerji Genel Müdürlüğü, Türkiye, EV-2018-01-V1, 2018.
  • [5] Yu X, Yan D, Sun K, Hong T, Zhu D, “Comparative study of the cooling energy performance of variable refrigerant flow systems and variable air volume systems in office buildings”, Applied Energy,183., 725–36., 2016.
  • [6] Costa A, Keane MM, Torrens JI, Corry E, “Building operation and energy performance: monitoring, analysis and optimization toolkit”. Applied Energy, 101., 310–316., 2013.
  • [7] Dhamneya, A. K., Rajput, S. P. S., & Singh, A, “Theoretical performance analysis of window air conditioner combined with evaporative cooling for better indoor thermal comfort and energy saving”, Journal of Building Engineering, 17., 52-64., 2018.
  • [8] Jadhav, T. S., & Lele, M. M, “Theoretical energy saving analysis of air conditioning system using heat pipe heat exchanger for Indian climatic zones”, Engineering Science and Technology, an International Journal, 18(4)., 669-673., 2015.
  • [9] Beypazarlı, Ş., Ayar, H., & Aktaş, M, “İklimlendirme Sistemlerinde Enerji Verimliliği ve Konfor Artişi Için Alternatif Bir Yöntemin Analizi”, İleri Teknoloji Bilimleri Dergisi, 5(2), 52-65., 2016.
  • [10] Söğüt, M. Z., & Karakoç, H, “Klimalarda Enerji Verimliliği Sınıflandırılmasında Farklı Bir Yaklaşım: Ekserjetik Verimlilik Oranı ve Çevresel Etki Oranı”, Tesisat Mühendisliği Dergisi, 135., 50-60., 2013.

Klima Santrallerinde Yoğuşan Suyun Geri Kazanımı İçin Alternatif Yöntemler

Yıl 2018, , 893 - 901, 01.08.2018
https://doi.org/10.29130/dubited.432814

Öz

Merkezi ısıtma ve soğutma
sistemlerinin en önemli parçası olan klima santrallerinde soğutucu serpantin
üzerinden büyük miktarda su yoğuşmakta ve bu su genellikle en yakın gidere verilmektedir.
Uygulamada da bu su, büyük bir atık olarak nitelendirilmektedir. Hâlbuki özellikle
%100 dış hava ile çalışan sistemlerdeki bu soğuk su depolanarak evaporatif
soğutma da dâhil olmak üzere birçok uygulamada değerlendirilebilir. Bu
çalışmada, klima santrallerinde yoğuşan suyun yeniden kullanımına yönelik farklı
tasarımlar önerilmiştir. Çalışmada üç farklı sistem üzerinde incelemeler
gerçekleştirilmiştir. Birinci sistemde %100 taze havalı bir klima santralinden
elde edilen yoğuşma suyunun, karışım havalı bir klima santralinin serpantininde
ön soğutucu olarak kullanılması incelenmiştir. İkinci sistemde ise %100 taze
havalı veya karışım havalı klima santralinin soğutucu serpantininde yoğuşan su
bir soğutma kuleli chiller cihazında besleme suyu olarak değerlendirilmesi
araştırılmıştır. Üçüncü sistemde ise %100 taze havalı veya karışım havalı klima
santralinin soğutucu serpantininde yoğuşan suyun hava soğutmalı kondenserli bir
chiller cihazında kullanımı incelenmiştir. Yapılan psikrometrik hesaplamalar,
%100 taze hava ile çalışan bir klima santralinde yaklaşık 80 kW’lık gizli
ısının, tasarlanan bu sistemler aracılığıyla duyulur ısı olarak
kullanılabileceğini göstermiştir.

Kaynakça

  • [1] Guo, Y., Tan, Z., Chen, H., Li, G., Wang, J., Huang, R., ... & Ahmad, T, “Deep learning-based fault diagnosis of variable refrigerant flow air-conditioning system for building energy saving”, Applied Energy, 225., 732-745., 2018.
  • [2] Hong T, Koo C, Kim J, Lee M, Jeong K, “A review on sustainable construction management strategies for monitoring, diagnosing, and retrofitting the building’s dynamic energy performance: focused on the operation and maintenance phase”, Applied Energy, 155., 671–707., 2015.
  • [3] Yang, L., Yan, H., & Lam, J. C, “Thermal comfort and building energy consumption implications–a review”, Applied Energy, 115., 164-173., 2014.
  • [4] “Türkiye enerji verimliliği gelişim raporu” Yenilenebilir Enerji Genel Müdürlüğü, Türkiye, EV-2018-01-V1, 2018.
  • [5] Yu X, Yan D, Sun K, Hong T, Zhu D, “Comparative study of the cooling energy performance of variable refrigerant flow systems and variable air volume systems in office buildings”, Applied Energy,183., 725–36., 2016.
  • [6] Costa A, Keane MM, Torrens JI, Corry E, “Building operation and energy performance: monitoring, analysis and optimization toolkit”. Applied Energy, 101., 310–316., 2013.
  • [7] Dhamneya, A. K., Rajput, S. P. S., & Singh, A, “Theoretical performance analysis of window air conditioner combined with evaporative cooling for better indoor thermal comfort and energy saving”, Journal of Building Engineering, 17., 52-64., 2018.
  • [8] Jadhav, T. S., & Lele, M. M, “Theoretical energy saving analysis of air conditioning system using heat pipe heat exchanger for Indian climatic zones”, Engineering Science and Technology, an International Journal, 18(4)., 669-673., 2015.
  • [9] Beypazarlı, Ş., Ayar, H., & Aktaş, M, “İklimlendirme Sistemlerinde Enerji Verimliliği ve Konfor Artişi Için Alternatif Bir Yöntemin Analizi”, İleri Teknoloji Bilimleri Dergisi, 5(2), 52-65., 2016.
  • [10] Söğüt, M. Z., & Karakoç, H, “Klimalarda Enerji Verimliliği Sınıflandırılmasında Farklı Bir Yaklaşım: Ekserjetik Verimlilik Oranı ve Çevresel Etki Oranı”, Tesisat Mühendisliği Dergisi, 135., 50-60., 2013.
Toplam 10 adet kaynakça vardır.

Ayrıntılar

Birincil Dil Türkçe
Konular Mühendislik
Bölüm Makaleler
Yazarlar

Ali Etem Gürel

İlhan Ceylan Bu kişi benim

Alper Ergün

Bahadır Acar

Yayımlanma Tarihi 1 Ağustos 2018
Yayımlandığı Sayı Yıl 2018

Kaynak Göster

APA Gürel, A. E., Ceylan, İ., Ergün, A., Acar, B. (2018). Klima Santrallerinde Yoğuşan Suyun Geri Kazanımı İçin Alternatif Yöntemler. Duzce University Journal of Science and Technology, 6(4), 893-901. https://doi.org/10.29130/dubited.432814
AMA Gürel AE, Ceylan İ, Ergün A, Acar B. Klima Santrallerinde Yoğuşan Suyun Geri Kazanımı İçin Alternatif Yöntemler. DÜBİTED. Ağustos 2018;6(4):893-901. doi:10.29130/dubited.432814
Chicago Gürel, Ali Etem, İlhan Ceylan, Alper Ergün, ve Bahadır Acar. “Klima Santrallerinde Yoğuşan Suyun Geri Kazanımı İçin Alternatif Yöntemler”. Duzce University Journal of Science and Technology 6, sy. 4 (Ağustos 2018): 893-901. https://doi.org/10.29130/dubited.432814.
EndNote Gürel AE, Ceylan İ, Ergün A, Acar B (01 Ağustos 2018) Klima Santrallerinde Yoğuşan Suyun Geri Kazanımı İçin Alternatif Yöntemler. Duzce University Journal of Science and Technology 6 4 893–901.
IEEE A. E. Gürel, İ. Ceylan, A. Ergün, ve B. Acar, “Klima Santrallerinde Yoğuşan Suyun Geri Kazanımı İçin Alternatif Yöntemler”, DÜBİTED, c. 6, sy. 4, ss. 893–901, 2018, doi: 10.29130/dubited.432814.
ISNAD Gürel, Ali Etem vd. “Klima Santrallerinde Yoğuşan Suyun Geri Kazanımı İçin Alternatif Yöntemler”. Duzce University Journal of Science and Technology 6/4 (Ağustos 2018), 893-901. https://doi.org/10.29130/dubited.432814.
JAMA Gürel AE, Ceylan İ, Ergün A, Acar B. Klima Santrallerinde Yoğuşan Suyun Geri Kazanımı İçin Alternatif Yöntemler. DÜBİTED. 2018;6:893–901.
MLA Gürel, Ali Etem vd. “Klima Santrallerinde Yoğuşan Suyun Geri Kazanımı İçin Alternatif Yöntemler”. Duzce University Journal of Science and Technology, c. 6, sy. 4, 2018, ss. 893-01, doi:10.29130/dubited.432814.
Vancouver Gürel AE, Ceylan İ, Ergün A, Acar B. Klima Santrallerinde Yoğuşan Suyun Geri Kazanımı İçin Alternatif Yöntemler. DÜBİTED. 2018;6(4):893-901.