Araştırma Makalesi

Evaluation of Drinking Water Network Chlorination Performance for Ondokuzmayıs District Using MİKE URBAN

Sayı: 15 31 Mart 2019
PDF İndir
EN TR

Evaluation of Drinking Water Network Chlorination Performance for Ondokuzmayıs District Using MİKE URBAN

Abstract

The quality of water must be suitable for the process until the last subscriber is treated from drinking water in the drinking water network. The chlorination process is an important process in order to keep certain parameters of water quality at certain intervals. The chlorination process must be managed in accordance with the drinking water demand. The operation of a drinking water network without the right chlorination strategy increases the cost of the water as well as the healthy transportation of the water to the end user point. The aim of this study is to create maps of chlorination according to seasons of Ondokuzmayıs district of Samsun and ensure implementation of correctly strategy. After collecting samples at predetermined time and points according to seasons at Ondokuzmayıs district, chlorine values were determined in laboratory. The average chlorine results measured at five points were found to be 1.2158 mg L-1 . After the determination of quality values of chlorine was identified, locations at MİKE URBAN water supply system geographic information system are defined according to each season. Value of chlorine in the entire network system Ondokuzmayıs district has been identified. By obtaining this data, city chlorination maps have been derived. At the maps, where and why chlorine value is low or high have been determined, and that must be followed correctly strategy has been created. 

Keywords

Kaynakça

  1. Günal, M. and Kösen,A., Application of GIS for Predicting Quality of Underground Water for Drinking.” ACTA PHYSICA POLONICA A,(2015) DOI: 10.12693/APhysPolA.128.B-107.
  2. Liu A., Egodawatta P., Kjolby M.J., Goonetilleke A. Development of pollutant build-up parameters for Mike Urban for Southeast Queensland, Australia, Proceedings of the International MIKE by DHI Conference (2010). Copenhagen, Denmark, P024.
  3. Monteiro L., Figueiredo D., Dias S., Freitas R., Covas D. , Menaia J. , Coelho S. T. Modeling of chlorine decay in drinking water supply systems using EPANET MSX, 12th International Conference on Computing and Control for the Water Industry, CCW12013, Procedia Engineering 70 (2014). 1192 - 1200.
  4. Muhammetoğlu H., Soyupak S., Karadirek İ. E. İçme suyu dağıtım şebekelerinde optimum klorlama uygulamalarının matematiksel modeller kullanılarak gerçekleştirilmesi ve dezenfeksiyon sistemlerinin yönetimi projesi el kitabı, Antalya Büyükşehir Belediye Başkanlığı, Antalya Su ve Atık Su İdaresi Genel Müdürlüğü, TUBİTAK-KAMAG 107G088 nolu proje, (2011). Antalya.
  5. Munavalli G. R. and Mohan Kumar M. S. Water quality parameter estimation in a distribution system under dynamic state, Water Research 39 (2005) 4287 - 4298. DOİ: 10.1016/j.watres.2005.07.043
  6. Oğur R., Tekbaş Ö. F., Hasde M. Klorlama rehberi, Gülhane Askeri Tıp Akademisi, Halk Sağlığı Anabilim Dalı, (2004) Ankara.
  7. Paraskevas D. Tzanavaras1, Demetrius G. Themelis , Fotini S. Kika. Review of analytical methods for the determination of chlorine dioxide. Central European Journal of Chemistry, Vol 5(1)(2007) 1–12, DOI: 10.2478/s11532-006-0054-9 Mini-review.
  8. Ulutaş M. B. Su dağıtım sistemlerinde su kalitesinin izlenmesi ve modellemesi, Yüksek lisans tezi, Ondokuzmayıs Üniversitesi, Fen Bilimleri Enstitüsü, Samsun, (2015) 425821.

Ayrıntılar

Birincil Dil

İngilizce

Konular

Mühendislik

Bölüm

Araştırma Makalesi

Yayımlanma Tarihi

31 Mart 2019

Gönderilme Tarihi

10 Aralık 2018

Kabul Tarihi

9 Mart 2019

Yayımlandığı Sayı

Yıl 2019 Sayı: 15

Kaynak Göster

APA
Şimşek, A., Ulutaş, M. B., & Bakan, G. (2019). Evaluation of Drinking Water Network Chlorination Performance for Ondokuzmayıs District Using MİKE URBAN. Avrupa Bilim ve Teknoloji Dergisi, 15, 368-374. https://doi.org/10.31590/ejosat.494521