Investigation of Thermal Comfort and Optimum Supply Water Temperature in the Double Layered Thermally Activated Building System

Cilt: 13 Sayı: 3 30 Eylül 2025
PDF İndir
EN TR

Investigation of Thermal Comfort and Optimum Supply Water Temperature in the Double Layered Thermally Activated Building System

Abstract

The adoption of low-temperature heating systems in buildings has become increasingly popular to reduce energy consumption and enhance energy efficiency. In our previous study, a novel hydronic radiant heating system integrating both Underfloor Heating and Thermally Activated Building Systems (TABS) on the same floor was developed. The optimization process was based on thermal comfort criteria defined in ASHRAE 55 and ISO 7730, using floor surface temperatures obtained via FLUENT/ANSYS simulations. The Generalized Reduced Gradient (GRG) algorithm was employed, with Predicted Mean Vote (PMV) and Predicted Percentage of Dissatisfaction (PPD) indicators to assess thermal comfort. Present study aims to optimize the supply water temperature for the "Double Layered Thermally Activated Building System" (DLTS), ensuring thermal comfort and energy efficiency. Results indicated that for thermal neutrality, the optimum supply water temperature was 26.66°C, and the optimum surface temperature was 23.60°C. The DLTS system met the comfort criteria with PPD values below 12.14 for class C, demonstrating high user satisfaction. This research highlights the potential of DLTS to improve both energy efficiency and thermal comfort in buildings, offering valuable insights for future building system designs.

Keywords

Kaynakça

  1. [1] Yıldız, C. 2024. Binalarda Enerji Verimliliğinde Son Gelişmeler: Türkiye Örneği. Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım ve Teknoloji, 12(1), 176-213.
  2. [2] Dino, İ. G. 2017. Binalarda Güneş Kontrol Yöntemlerinin Optimizasyon Temelli Performans Değerlendirilmesi. Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım ve Teknoloji, 5(3), 71-87.
  3. [3] Gündoğdu, E., Arslan, H. D. 2020. Mimaride Enerji Etkin Cephe Ve Biyomimikri. Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım ve Teknoloji, 8(4), 922-935.
  4. [4] Kalz, D.E., 2009. Heating and Cooling Concepts Employing Environmental Energy and Thermo-Active Building Systems for Low-Energy Buildings System Analysis and Optimization, Karlsruhe University Faculty of, PhD Thesis, Freiburg, 199 p.
  5. [5] Olesen, B. W., Liedelt, D. 2001. Cooling and heating of buildings by activating their thermal mass with embedded hydronic pipe systems. Proceedings of the ASHRAE-CIBSE, Dublin, Ireland, 3-4.
  6. [6] Olesen, B. W., Dossi, F. C. 2004. Operation and Control of Activated Slab Heating and Cooling Systems. Abstract from Procedings of CIB World Buildings Congress 2004, Toronto, Canada.
  7. [7] Olesen, B.W., Dossi, F.C., 2005. Neue erkenntnisse über regelung und betrieb für die betonkernaktivierung teil 1. HLH, 56 (1): 29-34.
  8. [8] Krarti, M., Ihm, P., 2005. Optimal control strategies for heated radiant floor systems, ASHRAE Transaction, 111(1): 535-546.

Ayrıntılar

Birincil Dil

İngilizce

Konular

Enerji

Bölüm

Araştırma Makalesi

Erken Görünüm Tarihi

29 Eylül 2025

Yayımlanma Tarihi

30 Eylül 2025

Gönderilme Tarihi

16 Temmuz 2025

Kabul Tarihi

9 Ağustos 2025

Yayımlandığı Sayı

Yıl 2025 Cilt: 13 Sayı: 3

Kaynak Göster

APA
Calisir, O., Öztürk, M., & Genç, G. (2025). Investigation of Thermal Comfort and Optimum Supply Water Temperature in the Double Layered Thermally Activated Building System. Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım ve Teknoloji, 13(3), 1315-1330. https://doi.org/10.29109/gujsc.1739629

                                     16168      16167     16166     21432        logo.png   


    e-ISSN:2147-9526