In this article, solar fraction of energy supply for the annual heating, cooling and domestic hot water requirement of a test room was investigated by using dynamic simulation technique. ClimateWell-Solar Cooling v1.1 build up with TRNSYS simulation programme was used in numerical analysis. The results showed that solar fraction of energy supply for the annual heating, cooling and domestic hot water of the test room are 63%, 99% and 99% respectively. It was obtained that annual average COP for cooling of the absorption system was 0,27 through the cooling period. 1296 TL economic savings and 11974 kg CO2 savings were achieved annually by using solar energy.
Bu çalışmada, dinamik simülasyon tekniği kullanılarak bir konfor odasının, yıl boyu ısıtma, soğutma ve sıcak su ihtiyacının güneş enerjisi ile karşılanması incelenmiştir. Çalışmada, TRNSYS programında oluşturulan ClimateWell-Solar Cooling v1.1 yazılımı kullanılmıştır. Çalışma sonucunda, güneş enerjisi sisteminin, konfor odasının yıllık ısıtma, soğutma ve sıcak kullanım suyu ihtiyacının güneş enerjisi ile karşılanma oranları sırasıyla, %63, %99 ve %99 olarak hesaplanmıştır. Absorbsiyonlu ısı pompası sisteminin soğutma periyodu boyunca soğutma tesir katsayısının yıllık ortalama değerinin 0,27 olduğu görülmüştür. Güneş enerjisinin kullanımı ile sağlanan enerji tasarrufuna bağlı olarak yıllık toplam 1296 TL ekonomik tasarruf elde edildiği ve CO2 salınımında 11974 kg’lık azalma sağlandığı tespit edilmiştir.
Birincil Dil | Türkçe |
---|---|
Konular | Mühendislik |
Bölüm | icindekiler-sunuş |
Yazarlar | |
Yayımlanma Tarihi | 1 Temmuz 2015 |
Gönderilme Tarihi | 1 Haziran 2015 |
Kabul Tarihi | 23 Haziran 2015 |
Yayımlandığı Sayı | Yıl 2015 Cilt: 56 Sayı: 666 |
Derginin DergiPark'a aktarımı devam ettiğinden arşiv sayılarına https://www.mmo.org.tr/muhendismakina adresinden erişebilirsiniz.
ISSN : 1300-3402
E-ISSN : 2667-7520